ASDA-B2
Chapter 7 Parameters
Revision May, 2018
7-33
P1-20
Reserved
Address: 0128H
0129H
P1-21
Reserved
Address: 012AH
012BH
P1-22
Reserved
Address: 012CH
012DH
P1-23
Reserved
Address: 012EH
012FH
P1-25
VSF1 Low-frequency Vibration Suppression (1)
Address: 0132H
0133H
Operation
Interface:
Panel/Software Communication
Related Section:
Section 6.2.9
Default:
1000
Control
Mode:
PT
Unit: 0.1Hz
Range: 10 ~ 1000
Data Size: 16bit
Format: DEC
Example
150 = 15 Hz
Settings: The setting value of the first low-frequency vibration suppression.
If P1-26 is set to 0, then it will disable the first low-frequency filter.
P1-26
VSG1
Low-frequency Vibration Suppression
Gain (1)
Address: 0134H
0135H
Operation
Interface:
Panel/Software Communication
Related Section:
Section 6.2.9
Default:
0
Control
Mode:
PT
Unit: -
Range: 0~9 (0: Disable the first low-frequency
filter)
Data Size: 16bit
Format: DEC
Settings: The first low-frequency vibration suppression gain. The bigger
value it is, the better the position response will be. However, if the
value is set too big, the motor will not be able to smoothly
operate. It is suggested to set the value to 1.
Содержание ASD-B2-1521-F
Страница 1: ......
Страница 20: ...ASDA B2 Chapter 1 Installation and Model Explanation Revision May 2018 1 7 1 4 Servo Drive Features...
Страница 81: ...Chapter 3 Wiring ASDA B2 3 42 Revision May 2018 This page is intentionally left blank...
Страница 103: ...Chapter 5 Trial Operation and Tuning ASDA B2 5 12 Revision May 2018 5 5 2 Inertia Estimation Flowchart with Mechanism...
Страница 124: ...ASDA B2 Chapter 6 Control Modes of Operation Revision May 2018 6 13...