Chapter 6 Control Modes of Operation
ASDA-B2
6-30
Revision May, 2018
P2-45
NCF3 Resonance Suppression (Notch Filter) 3
Address: 025AH
025BH
Operation
Interface:
Panel/Software
Communication
Related Section:
Section 6.3.7
Default:
1000
Control
Mode:
ALL
Unit: Hz
Range: 50 ~ 2000
Data Size: 16-bit
Display
Format:
Decimal
Settings: The third group of mechanism resonance frequency setting value.
If P2-46 is set to 0, this function will be disabled. P2-23 and
P2-24 are the first group of resonance suppression (Notch filter).
P2-46
DPH3
Resonance Suppression (Notch Filter)
Attenuation Rate (3)
Address: 025CH
025DH
Operation
Interface:
Panel/Software
Communication
Related Section:
Section 6.3.7
Default:
0
Control
Mode:
ALL
Unit: dB
Range: 0 ~ 32
Data Size: 16-bit
Display
Format:
Decimal
Settings: The third group of resonance suppression (Notch filter)
attenuation rate. Set the value to 0 to disable the function of
Notch filter.