Chapter 7 Parameters
Revision May, 2018
7-53
P2-06
KVI Speed Integral Compensation
Address: 020CH
020DH
Operation
Interface:
Panel/Software
Communication
Related Section:
6.3.6
Default:
100
Control
Mode:
ALL
Unit: rad/s
Range: 0 ~ 1023
Data Size: 16-bit
Format: Decimal
Settings: Increasing the value of speed integral compensation can enhance
speed response and diminish the deviation of speed control.
However, if the value is set too big, it would easily cause
resonance and noise.
P2-07
KVF Speed Feed Forward Gain
Address: 020EH
020FH
Operation
Interface:
Panel/Software
Communication
Related Section:
6.3.6
Default:
0
Control
Mode:
ALL
Unit: %
Range: 0 ~ 100
Data Size: 16-bit
Format: Decimal
Settings: When the speed control command runs smoothly, increasing the
gain value can reduce the speed command error. If the command
does not run smoothly, decreasing the gain value can reduce the
mechanical vibration during operation.
P2-08
■
PCTL Special Parameter Write-in
Address: 0210H
0211H
Operation
Interface:
Panel/Software
Communication
Related Section: N/A
Default:
0
Control
Mode:
ALL
Unit: N/A
Range: 0 ~ 65535
Data Size: 16-bit
Format: Decimal
Содержание ASD-B2-1521-F
Страница 1: ......
Страница 20: ...ASDA B2 Chapter 1 Installation and Model Explanation Revision May 2018 1 7 1 4 Servo Drive Features...
Страница 81: ...Chapter 3 Wiring ASDA B2 3 42 Revision May 2018 This page is intentionally left blank...
Страница 103: ...Chapter 5 Trial Operation and Tuning ASDA B2 5 12 Revision May 2018 5 5 2 Inertia Estimation Flowchart with Mechanism...
Страница 124: ...ASDA B2 Chapter 6 Control Modes of Operation Revision May 2018 6 13...