Chapter 5 Trial Operation and Tuning
ASDA-B2
5-8
Revision May, 2018
5.4 Trial Run without Load (Speed Mode)
Before the trial run without load, firmly secure the motor base so as to avoid the danger
cause by the reaction of motor operation.
STEP 1:
Set the control mode of the servo drive to speed mode. Set P1-01 to 2. Then, re-power on
the servo drive.
STEP 2:
In speed control mode, the digital input settings of trial run are as follows:
Digital Input
Parameter
Setting Value
Symbol
Function Description
CN1 PIN No.
DI1
P2-10 = 101
SON
Servo On
DI1- = 9
DI2
P2-11 = 109
TRQLM
Torque limit
DI2- = 10
DI3
P2-12 = 114
SPD0
Speed command selection
DI3- = 34
DI4
P2-13 = 115
SPD1
Speed command selection
DI4- = 8
DI5
P2-14 = 102
ARST
Alarm reset
DI5- = 33
DI6
P2-15 = 0
Disabled
Invalid DI function
-
DI7
P2-16 = 0
Disabled
Invalid DI function
-
DI8
P2-17 = 0
Disabled
Invalid DI function
-
DI9
P2-36 = 0
Disabled
Invalid DI function
-
The above table disables the function of negative limit (DI6), positive limit (DI7) and
emergency stop (DI8). Thus, the value of parameter P2-15 ~ P2-17 and P2-36 is set to 0
(Disabled). The digital input of Delta’s servo drive can be programmed by users. When
programming digital input, please refer to the description of DI code.
The default setting includes the function of negative limit, positive limit and emergency
stop, therefore, after the setting is completed, if there is any alarm occurs, please re-power
on the servo drive or switch ON DI5 to clear the alarm. Please refer to Chapter 5.2.
Содержание ASD-B2-1521-F
Страница 1: ......
Страница 20: ...ASDA B2 Chapter 1 Installation and Model Explanation Revision May 2018 1 7 1 4 Servo Drive Features...
Страница 81: ...Chapter 3 Wiring ASDA B2 3 42 Revision May 2018 This page is intentionally left blank...
Страница 103: ...Chapter 5 Trial Operation and Tuning ASDA B2 5 12 Revision May 2018 5 5 2 Inertia Estimation Flowchart with Mechanism...
Страница 124: ...ASDA B2 Chapter 6 Control Modes of Operation Revision May 2018 6 13...