ASDA-B2
Chapter 9 Troubleshooting
Revision May, 2018
9-15
9.3 Corrective Actions after the Alarm Occurs
AL001
Over current
Turn DI.ARST on to clear the alarm
AL002
Over voltage
Turn DI.ARST on to clear the alarm
AL003
Under voltage
Cycle power on the servo drive to
clear the alarm.
For the alarm to clear automatically
after the voltage returns to normal,
please set with P2-66 Bit2.
AL004
The magnetic field of the motor is
abnormal
The alarm can be cleared after re-
power on.
AL005
Regeneration error
Turn DI.ARST on to clear the alarm
AL006
Overload
Turn DI.ARST on to clear the alarm
AL007
Excessive speed deviation
Turn DI.ARST on to clear the alarm
AL008
Abnormal pulse command
Turn DI.ARST on to clear the alarm
AL009
Excessive deviation of position
control
Turn DI.ARST on to clear the alarm
AL011
Encoder error
The alarm can be cleared after
re-power on.
AL012
Adjustment error
The alarm can be cleared when
removing CN1 wiring and execute
auto adjustment.
AL013
Emergency stop
The alarm can be cleared
automatically after turning DI.EMGS
off.
AL014
Reverse limit error
Turn DI.ARST on or Servo Off to
clear the alarm. The alarm also can
be cleared when the motor operates
backwards.
AL015
Forward limit error
Turn DI.ARST on or Servo Off to
clear the alarm. The alarm also can
be cleared when the motor operates
backwards.
AL016
The temperature of IGBT is abnormal
error
Turn DI.ARST on to clear the alarm
AL017
Abnormal EEPROM
If the alarm occurs, then parameter
reset is a must. And re-servo on
again. If it happens during the
operation, please turn DI.ARST on
to clear the alarm.
AL018
Abnormal signal
Turn DI.ARST on to clear the alarm
Содержание ASD-B2-1521-F
Страница 1: ......
Страница 20: ...ASDA B2 Chapter 1 Installation and Model Explanation Revision May 2018 1 7 1 4 Servo Drive Features...
Страница 81: ...Chapter 3 Wiring ASDA B2 3 42 Revision May 2018 This page is intentionally left blank...
Страница 103: ...Chapter 5 Trial Operation and Tuning ASDA B2 5 12 Revision May 2018 5 5 2 Inertia Estimation Flowchart with Mechanism...
Страница 124: ...ASDA B2 Chapter 6 Control Modes of Operation Revision May 2018 6 13...