Chapter 7 Parameters
ASDA-B2
7-54
Revision May, 2018
Settings: Special parameter write-in:
Parameter
code
Function
10
Reset the parameter (Apply to the power
again after reset)
20
P4-10 is writable
22
P4-11~P4-21are writable
406
Enable forced DO mode
400
When forced DO mode is enabled, it can
switch back to the normal DO mode.
Password protective setting:
1. Enter 5-digit number, press the same password again (The top
digit should be 1 at least.).
2. Re-power on the servo drive, the protective funciton will be
activated immediately.
Parameter setting after setting up the password:
When entering the correct password, the parameter can be set.
Clear the password: After entering the correct password, please
enter “0” twice continuously.
P2-09
DRT DI Debouncing Time
Address: 0212H
0213H
Operation
Interface:
Panel/Software
Communication
Related Section: N/A
Default:
2
Control
Mode:
ALL
Unit: 2ms
Range: 0 ~ 20
Data Size: 16-bit
Format: Decimal
Example: 4 = 8 ms
Settings: When the environmental noise is big, increasing the setting value
can enhance the control stability. However, if the value is set too
big, the response time will be influenced.
Содержание ASD-B2-1521-F
Страница 1: ......
Страница 20: ...ASDA B2 Chapter 1 Installation and Model Explanation Revision May 2018 1 7 1 4 Servo Drive Features...
Страница 81: ...Chapter 3 Wiring ASDA B2 3 42 Revision May 2018 This page is intentionally left blank...
Страница 103: ...Chapter 5 Trial Operation and Tuning ASDA B2 5 12 Revision May 2018 5 5 2 Inertia Estimation Flowchart with Mechanism...
Страница 124: ...ASDA B2 Chapter 6 Control Modes of Operation Revision May 2018 6 13...