Chapter 7 Parameters
ASDA-B2
7-82
Revision May, 2018
P3-03
FLT Communication Error Disposal
Address: 0306H
0307H
Operation
Interface:
Panel / Software
Communication
Related Section:
8.2
Default:
0
Control
Mode:
ALL
Unit: N/A
Range: 0 ~ 1
Data Size: 16-bit
Format: Hexadecimal
Settings: The definition of the setting value is as the following:
0: Warning and keeps running
1: Warning and stops deceleration (The deceleration time is set to
parameter P1-32)
P3-04
CWD Communication Time Out
Address: 0308H
0309H
Operation
Interface:
Panel / Software
Communication
Related Section:
8.2
Default:
0
Control
Mode:
ALL
Unit: sec
Range: 0 ~ 20
Data Size: 16-bit
Format: Decimal
Settings: If the setting value is not 0, enable communication timeout
immediately. If it is set to 0, disable the function.
P3-05
CMM Communication Mechanism
Address: 030AH
030BH
Operation
Interface:
Panel / Software
Communication
Related Section:
8.2
Default:
0
Control
Mode:
ALL
Unit: N/A
Range: 0x00 ~ 0x01
Data Size: 16-bit
Format: Hexadecimal
Settings: RS-232 via MOBUS communication or communicate with
ASDA-Soft
RS-232 Communication format
0: RS-232/RS485 via Modbus communication
1: RS-232 upon ASDA-Soft software
Содержание ASD-B2-1521-F
Страница 1: ......
Страница 20: ...ASDA B2 Chapter 1 Installation and Model Explanation Revision May 2018 1 7 1 4 Servo Drive Features...
Страница 81: ...Chapter 3 Wiring ASDA B2 3 42 Revision May 2018 This page is intentionally left blank...
Страница 103: ...Chapter 5 Trial Operation and Tuning ASDA B2 5 12 Revision May 2018 5 5 2 Inertia Estimation Flowchart with Mechanism...
Страница 124: ...ASDA B2 Chapter 6 Control Modes of Operation Revision May 2018 6 13...