Parameters and firmware blocks
230
62.21
POS COR MODE
(see above)
Determines if the position change made in homing or in preset mode 2 or 3 is forced permanently into
the drive memory by saving it to parameter
, or only until the next power-
down.
(0)
Normal
The position change made in homing or in preset mode 2 or 3 is
effective only until the next power-down.
(1)
Permanent
The position change made in homing or in preset mode 2 or 3 remains
permanently effective.
62.22
TRIG PROBE1 SW
(see above)
Selects the source of the trigger probe 1 signal. The selection is active when parameter
is set to
.
Example: P.2.1.4 (P. DI STATUS.4) selects digital input DI5 of the drive control board as the trigger
probe 1 signal.
Bit pointer: Group, index and bit.
62.23
TRIG PROBE2 SW
(see above)
Selects the source of the trigger probe 2 signal. The selection is active when parameter
is set to
.
Bit pointer: Group, index and bit.
62.25
Z-PULSE SOURCE 1
(see above)
Selects which zero pulse is used for probe 1 latching when a zero pulse dependent triggering
condition is selected by parameter
(0)
ProbePosSrc
The source of the zero pulse is the same as the source of the position
data (see parameter
).
(1)
Encoder 1
Zero pulse from encoder 1 used.
Note:
If the position data and zero pulse sources are not the same (ie,
the position data is received from encoder 2, and parameters
are set to different
values), encoders 1 and 2 must be connected to the same FEN-xx
extension anyway. In addition, the logic version of the FEN-xx must be
VIEx1500 or later.
(2)
Encoder 2
Zero pulse from encoder 2 used.
Note:
If the position data and zero pulse sources are not the same (ie,
the position data is received from encoder 1, and parameters
are set to different
values), encoders 1 and 2 must be connected to the same FEN-xx
extension anyway. In addition, the logic version of the FEN-xx must be
VIEx1500 or later.
(3)
Emulated Zp
Emulated zero pulse used.
Notes:
• The logic version of the FEN-xx must be VIEx1500 or later.
• Encoder emulation must be properly activated by parameters
. See also
.
Содержание ACSM1 Series
Страница 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Страница 4: ......
Страница 34: ...Drive programming using PC tools 34 ...
Страница 86: ...Drive control and features 86 ...
Страница 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Страница 302: ...Parameter data 302 ...
Страница 422: ...Application program template 422 ...
Страница 430: ...Appendix A Fieldbus control 430 ...
Страница 500: ...Appendix D Application examples 500 ...
Страница 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Страница 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...