Standard function blocks
379
Operation
The block controls the analogue output (AO1) of a FIO-11 Analog I/O Extension
mounted on slot 2 of the drive control unit.
The block converts the input signal (AO scaled) to a 0…20 mA signal (AO) that drives
the analogue output; the input range AO Min Scale … AO Max Scale corresponds to
the current signal range of AO Min … AO Max.
AO Min Scale must be smaller than AO Max Scale; AO Max can be greater or smaller
than AO Min.
Inputs
Minimum current signal (AO Min): REAL (0…20 mA)
Maximum current signal (AO Max): REAL (0…20 mA)
Minimum input signal (AO Min Scale): REAL
Maximum input signal (AO Max Scale): REAL
Input signal (AO scaled): REAL
Outputs
Analogue output current value (AO): REAL
Error output (Error): DINT (0 = No error; 1 = Application program memory full)
AO [mA]
0
20
AO scaled
32768
-32768
0
AO Max S
cale
AO Min Scale
AO Max
AO Min
AO Min < AO Max
AO Min > AO Max
AO [mA]
0
20
AO scaled
32768
-32768
0
AO Max S
cale
AO Min Scale
AO Max
AO Min
Содержание ACSM1 Series
Страница 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Страница 4: ......
Страница 34: ...Drive programming using PC tools 34 ...
Страница 86: ...Drive control and features 86 ...
Страница 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Страница 302: ...Parameter data 302 ...
Страница 422: ...Application program template 422 ...
Страница 430: ...Appendix A Fieldbus control 430 ...
Страница 500: ...Appendix D Application examples 500 ...
Страница 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Страница 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...