Fault tracing
315
0005
DC UNDERVOLTAGE
(0x3220)
Intermediate circuit DC voltage
is not sufficient due to missing
mains phase, blown fuse or
rectifier bridge internal fault.
Check mains supply and fuses.
0006
EARTH FAULT
(0x2330)
Programmable fault:
Drive has detected load
unbalance typically due to earth
fault in motor or motor cable.
Check that there are no power factor
correction capacitors or surge absorbers in
motor cable.
Check that there is no earth fault in motor or
motor cables:
- measure insulation resistances of motor and
motor cable.
If no earth fault can be detected, contact your
local ABB representative.
0007
FAN FAULT
(0xFF83)
Fan is not able to rotate freely or
fan is disconnected. Fan
operation is monitored by
measuring fan current.
Check fan operation and connection.
0008
IGBT OVERTEMP
(0x7184)
Drive temperature based on
thermal model has exceeded
internal fault limit.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against unit power.
0009
BC WIRING
(0x7111)
Braking resistor is missing,
damaged or there is a problem
in the resistor cabling.
Short circuit in the braking
chopper IGBT.
Ensure that the braking resistor is connected
and not damaged.
Replace the braking chopper.
0010
BC SHORT CIRCUIT
(0x7113)
Short circuit in the braking
chopper IGBT.
Ensure that the braking resistor is connected
and not damaged.
Replace the braking chopper.
0011
BC OVERHEAT
(0x7181)
Braking chopper IGBT
temperature has exceeded
internal fault limit.
Let chopper cool down.
Check for excessive ambient temperature.
Check for cooling fan failure.
Check for obstructions in the air flow.
Check the dimensioning and cooling of the
cabinet.
Check resistor overload protection function
settings, parameters
Check that braking cycle meets allowed
limits.
Check that drive supply AC voltage is not
excessive.
Code
Fault
(fieldbus code)
Cause
What to do
Содержание ACSM1 Series
Страница 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Страница 4: ......
Страница 34: ...Drive programming using PC tools 34 ...
Страница 86: ...Drive control and features 86 ...
Страница 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Страница 302: ...Parameter data 302 ...
Страница 422: ...Application program template 422 ...
Страница 430: ...Appendix A Fieldbus control 430 ...
Страница 500: ...Appendix D Application examples 500 ...
Страница 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Страница 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...