Parameters and firmware blocks
208
50.12
FBA CYCLE TIME
(see above)
Selects the fieldbus communication speed. The default selection is
. Lowering the speed
reduces the CPU load.
The table below shows the read/write intervals for cyclic and cyclic low data with each parameter
setting.
*Cyclic data consists of fieldbus CW and SW, Ref1 and Ref2, and Act1 and Act2.
**Cyclic low data consists of the parameter data mapped to parameter groups
(0)
Slow
Slow speed selected.
(1)
Normal
Normal speed selected.
(2)
Fast
Fast speed selected.
50.20
FB MAIN SW FUNC
(see above)
Contains various compatibility settings especially for drive retrofits.
Selection
Cyclic*
Cyclic low*
Slow
10 ms
10 ms
Normal
2 ms
10 ms
Fast
500 us
2 ms
Bit
Name
Information
0
Run enable func 1 = Parameter only:
Bit 1 of
is set to 1 whenever the external run
enable signal (par.
) is 1.
0 = Param AND Fb cw:
Bit 1 of
is set to 1 whenever both the external
run enable signal (par.
) is 1 AND
bit 7 (RUN ENABLE) are 1.
1
Mech brake func 1 = Force ramp stop:
Drive always uses ramp stop when a mechanical brake is used.
0 = Allow coast stop:
Coast stop is allowed when a mechanical brake is used.
Содержание ACSM1 Series
Страница 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Страница 4: ......
Страница 34: ...Drive programming using PC tools 34 ...
Страница 86: ...Drive control and features 86 ...
Страница 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Страница 302: ...Parameter data 302 ...
Страница 422: ...Application program template 422 ...
Страница 430: ...Appendix A Fieldbus control 430 ...
Страница 500: ...Appendix D Application examples 500 ...
Страница 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Страница 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...