Standard function blocks
361
Counters
CTD
(10047)
Illustration
Execution time
0.92 µs
Operation
The counter output (CV) value is decreased by 1 if the counter input (CD) value
changes from 0 -> 1 and the load input (LD) value is 0. If the load input value is 1, the
preset input (PV) value is stored as the counter output (CV) value. If the counter output
has reached its minimum value -32768, the counter output remains unchanged.
The status output (Q) is 1 if the counter output (CV) value < 0.
Example:
Inputs
Load input (LD): Boolean
Counter input (CD): Boolean
Preset input (PV): INT
Outputs
Counter output (CV): INT
Status output (Q): Boolean
CTD
93
TLA1 1 msec
(1)
LD
>CD
PV
CV
CV(93)
Q
Q(93)
LD
CD
PV
Q
CV
prev
CV
0
1 -> 0
10
0
5
5
0
0 -> 1
10
0
5
5 - 1 = 4
1
1 -> 0
-2
1
4
-2
1
0 -> 1
1
0
-2
1
0
0 -> 1
5
1
1
1 -1 = 0
1
1 -> 0
-32768
1
0
-32768
0
0 -> 1
10
1
-32768
-32768
CV
prev
is the previous cycle counter output value.
Содержание ACSM1 Series
Страница 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Страница 4: ......
Страница 34: ...Drive programming using PC tools 34 ...
Страница 86: ...Drive control and features 86 ...
Страница 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Страница 302: ...Parameter data 302 ...
Страница 422: ...Application program template 422 ...
Страница 430: ...Appendix A Fieldbus control 430 ...
Страница 500: ...Appendix D Application examples 500 ...
Страница 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Страница 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...