Standard function blocks
357
INT_TO_BOOL
(10024)
Illustration
Execution time
4.31 µs
Operation
The boolean output (OUT1…OUT16) values are formed from the 16-bit integer input
(IN) value.
Example:
Inputs
Input (IN): INT
Outputs
Output (OUT1…OUT16): Boolean
Sign output (SIGN): Boolean
INT_TO_BOOL
87
TLA1 1 msec
(1)
IN
OUT1
OUT1(87)
OUT2
OUT2(87)
OUT3
OUT3(87)
OUT4
OUT4(87)
OUT5
OUT5(87)
OUT6
OUT6(87)
OUT7
OUT7(87)
OUT8
OUT8(87)
OUT9
OUT9(87)
OUT10
OUT10(87)
OUT11
OUT11(87)
OUT12
OUT12(87)
OUT13
OUT13(87)
OUT14
OUT14(87)
OUT15
OUT15(87)
OUT16
OUT16(87)
SIGN
SIGN(87)
IN = 0111 1111 1111 1111
OUT16…OUT1
SIGN