![ABB ACSM1 Series Скачать руководство пользователя страница 316](http://html.mh-extra.com/html/abb/acsm1-series/acsm1-series_manual_2326316.webp)
Fault tracing
316
0012
BR OVERHEAT
(0x7112)
Braking resistor temperature
has exceeded fault limit defined
by parameter
.
Stop drive. Let resistor cool down.
Check resistor overload protection function
settings, parameters
Check fault limit setting, parameter
.
Check that braking cycle meets allowed
limits.
0013
CURR MEAS GAIN
(0x3183)
Difference between output
phase U2 and W2 current
measurement gain is too great.
Contact your local ABB representative.
0014
CABLE CROSS CON
(0x3181)
Programmable fault:
Incorrect input power and motor
cable connection (ie, input
power cable is connected to
drive motor connection).
Check input power connections. This fault
can be disabled after the drive has been
commissioned until the input power cable or
motor cable are disconnected again.
0015
SUPPLY PHASE
(0x3130)
Programmable fault:
Intermediate circuit DC voltage
is oscillating due to missing
input power line phase or blown
fuse.
Check input power line fuses.
Check for input power supply imbalance.
0016
MOTOR PHASE
(0x3182)
Programmable fault:
Motor circuit fault due to
missing motor connection (all
three phases are not
connected).
Connect motor cable.
Code
Fault
(fieldbus code)
Cause
What to do
Содержание ACSM1 Series
Страница 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Страница 4: ......
Страница 34: ...Drive programming using PC tools 34 ...
Страница 86: ...Drive control and features 86 ...
Страница 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Страница 302: ...Parameter data 302 ...
Страница 422: ...Application program template 422 ...
Страница 430: ...Appendix A Fieldbus control 430 ...
Страница 500: ...Appendix D Application examples 500 ...
Страница 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Страница 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...