Standard function blocks
366
CTUD_DINT
(10050)
Illustration
Execution time
1.40 µs
Operation
The counter output (CV) value is increased by 1 if the counter input (CU) changes from
0 -> 1 and the reset input (R) is 0 and the load input (LD) is 0.
The counter output (CV) value is decreased by 1 if the counter input (CD) changes from
0 -> 1 and the load input (LD) is 0 and the reset input (R) is 0.
If the counter output has reached its minimum or maximum value, -2147483648 or
+2147483647, the counter output remains unchanged until it is reset (R) or until the load
input (LD) is set to 1.
If the load input (LD) value is 1, the preset input (PV) value is stored as the counter
output (CV) value.
The counter output (CV) is reset to 0 if the reset input (R) is 1.
The up counter status output (QU) is 1 if the counter output (CV) value > preset input
(PV) value.
The down counter status output (QD) is 1 if the counter output (CV) value < 0.
Example:
CTUD_DINT
98
TLA1 1 msec
(1)
>CU
>CD
R
LD
PV
CV
CV(98)
QU
QU(98)
QD
QD (98)
CU
CD
R
LD
PV
QU
QD
CV
prev
CV
0 -> 0
0 -> 0
0
0
2
0
1
0
0
0 -> 0
0 -> 0
0
1
2
1
0
0
2
0 -> 0
0 -> 0
1
0
2
0
1
2
0
0 -> 0
0 -> 0
1
1
2
0
1
0
0
0 -> 0
0 -> 1
0
0
2
0
1
0
0 - 1 = -1
0 -> 0
1 -> 1
0
1
2
1
0
-1
2
0 -> 0
1 -> 1
1
0
2
0
1
2
0
0 -> 0
1 -> 1
1
1
2
0
1
0
0
0 -> 1
1 -> 0
0
0
2
0
0
0
0 + 1 = 1
1 -> 1
0 -> 0
0
1
2
1
0
1
2
1 -> 1
0 -> 0
1
0
2
0
1
2
0
1 -> 1
0 -> 0
1
1
2
0
1
0
0
1 -> 1
0 -> 1
0
0
2
0
1
0
0 - 1 = -1
1 -> 1
1 -> 1
0
1
2
1
0
-1
2
1 -> 1
1 -> 1
1
0
2
0
1
2
0
1 -> 1
1 -> 1
1
1
2
0
1
0
0
CV
prev
is the previous cycle counter output value.
Содержание ACSM1 Series
Страница 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Страница 4: ......
Страница 34: ...Drive programming using PC tools 34 ...
Страница 86: ...Drive control and features 86 ...
Страница 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Страница 302: ...Parameter data 302 ...
Страница 422: ...Application program template 422 ...
Страница 430: ...Appendix A Fieldbus control 430 ...
Страница 500: ...Appendix D Application examples 500 ...
Страница 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Страница 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...