Fault tracing
314
Fault messages generated by the drive
Code
Fault
(fieldbus code)
Cause
What to do
0001
OVERCURRENT
(0x2310)
Output current has exceeded
internal fault limit.
Check motor load.
Check acceleration time. See parameter
group
on page
Check motor and motor cable (including
phasing and delta/star connection).
Check that the start-up data in parameter
group
corresponds to the motor rating
plate.
Check that there are no power factor
correction capacitors or surge absorbers in
motor cable.
Check encoder cable (including phasing).
0002
DC OVERVOLTAGE
(0x3210)
Excessive intermediate circuit
DC voltage.
Check that overvoltage controller is on,
parameter
.
Check mains for static or transient
overvoltage.
Check braking chopper and resistor (if used).
Check deceleration time.
Use coast-to-stop function (if applicable).
Retrofit frequency converter with braking
chopper and braking resistor.
0003
DEVICE OVERTEMP
(0x4210)
Measured drive temperature
has exceeded internal fault limit.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against unit power.
0004
SHORT CIRCUIT
(0x2340)
Short-circuit in motor cable(s) or
motor.
Check motor and motor cable.
Check that there are no power factor
correction capacitors or surge absorbers in
motor cable.
Check the braking chopper cabling.
Extension: 1
Short-circuit in the upper
transistor of the U-phase.
Contact your local ABB representative.
Extension: 2
Short-circuit in the lower
transistor of the U-phase.
Contact your local ABB representative.
Extension: 4
Short-circuit in the upper
transistor of the V-phase.
Contact your local ABB representative.
Extension: 8
Short-circuit in the lower
transistor of the V-phase.
Contact your local ABB representative.
Extension: 16
Short-circuit in the upper
transistor of the W-phase.
Contact your local ABB representative.
Extension: 32
Short-circuit in the lower
transistor of the W-phase.
Contact your local ABB representative.
Содержание ACSM1 Series
Страница 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Страница 4: ......
Страница 34: ...Drive programming using PC tools 34 ...
Страница 86: ...Drive control and features 86 ...
Страница 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Страница 302: ...Parameter data 302 ...
Страница 422: ...Application program template 422 ...
Страница 430: ...Appendix A Fieldbus control 430 ...
Страница 500: ...Appendix D Application examples 500 ...
Страница 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Страница 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...