Parameters and firmware blocks
139
15.09
AO2 MAX
(see above)
Defines the maximum value for analogue output AO2.
-10…10 V
Maximum AO2 output value.
15.10
AO2 MIN
(see above)
Defines the minimum value for analogue output AO2.
-10…10 V
Minimum AO2 output value.
15.11
AO2 MAX SCALE
(see above)
Defines the real value that corresponds to the maximum analogue output value defined by
parameter
-32768…32767
Real value corresponding to value of parameter
15.12
AO2 MIN SCALE
(see above)
Defines the real value that corresponds to the minimum analogue output value defined by
parameter
. See parameter
-32768…32767
Real value corresponding to value of parameter
AO
(real)
AO
(real)
AO
(V)
AO
(V)