![ABB ACSM1 Series Скачать руководство пользователя страница 311](http://html.mh-extra.com/html/abb/acsm1-series/acsm1-series_manual_2326311.webp)
Fault tracing
311
2031
ENCODER 1 CABLE
(0x7389)
Encoder 1 cable fault detected.
Check cable between FEN-xx interface and
encoder 1. After any modifications in cabling,
re-configure interface by switching drive
power off and on, or by activating parameter
2032
ENCODER 2 CABLE
(0x738A)
Encoder 2 cable fault detected.
Check cable between FEN-xx interface and
encoder 2. After any modifications in cabling,
re-configure interface by switching drive
power off and on, or by activating parameter
2033
D2D COMMUNICATION
(0x7520)
Programmable fault:
On the master drive: The drive
has not been replied to by an
activated follower for five
consecutive polling cycles.
Check that all drives that are polled
(parameters
) on the drive-to-
drive link are powered, properly connected to
the link, and have the correct node address.
Check the drive-to-drive link wiring.
On a follower drive: The drive
has not received new reference
1 and/or 2 for five consecutive
reference handling cycles.
Check the settings of parameters
and
on the master drive.
Check the drive-to-drive link wiring.
2034
D2D BUFFER
OVERLOAD
(0x7520)
Programmable fault:
Transmission of drive-to-drive
references failed because of
message buffer overflow.
Contact your local ABB representative.
2035
PS COMM
(0x5480)
Communication errors detected
between the JCU Control Unit
and the power unit of the drive.
Check the connections between the JCU
Control Unit and the power unit.
If the JCU is powered from an external
supply, ensure that parameter
is set to
.
2036
RESTORE
(0x630D)
Restoration of backed-up
parameters failed.
Contact your local ABB representative.
2037
CUR MEAS
CALIBRATION
(0x2280)
Current measurement
calibration will occur at next
start.
Informative alarm.
2038
AUTOPHASING
(0x3187)
Autophasing will occur at next
start.
Informative alarm.
2039
EARTH FAULT
(0x2330)
Programmable fault:
Drive has detected load
unbalance typically due to earth
fault in motor or motor cable.
Check that there are no power factor
correction capacitors or surge absorbers in
motor cable.
Check that there is no earth fault in motor or
motor cables:
- measure insulation resistances of motor and
motor cable.
If no earth fault can be detected, contact your
local ABB representative.
Code
Alarm
(fieldbus code)
Cause
What to do
Содержание ACSM1 Series
Страница 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Страница 4: ......
Страница 34: ...Drive programming using PC tools 34 ...
Страница 86: ...Drive control and features 86 ...
Страница 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Страница 302: ...Parameter data 302 ...
Страница 422: ...Application program template 422 ...
Страница 430: ...Appendix A Fieldbus control 430 ...
Страница 500: ...Appendix D Application examples 500 ...
Страница 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Страница 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...