Parameters and firmware blocks
215
57.03
NODE ADDRESS
(see above)
Sets the node address for a follower drive. Each follower must have a dedicated node address.
Note:
If the drive is set to be the master on the drive-to-drive link, this parameter has no effect (the
master is automatically assigned node address 0).
1…62
Node address.
57.04
FOLLOWER MASK 1
(see above)
On the master drive, selects the followers to be polled. If no response is received from a polled
follower, the action selected by parameter
is taken.
The least significant bit represents follower with node address 1, while the most significant bit
represents follower 31. When a bit is set to 1, the corresponding node address is polled. For example,
followers 1 and 2 are polled when this parameter is set to the value of 0x3.
0x00000000…0x7FFFFFFF
Follower mask 1.
57.05
FOLLOWER MASK 2
(see above)
On the master drive, selects the followers to be polled. If no response is received from a polled
follower, the action selected by parameter
is taken.
The least significant bit represents follower with node address 32, while the most significant bit
represents follower 62. When a bit is set to 1, the corresponding node address is polled. For example,
followers 32 and 33 are polled when this parameter is set to the value of 0x3.
0x00000000…0x7FFFFFFF
Follower mask 2.
57.06
REF 1 SRC
(see above)
Selects the source of D2D reference 1 sent to the followers. The parameter is effective on the master
drive, as well as submasters (
=
) in a multicast
message chain (see parameter
The default value is P.03.04, ie,
.
Value pointer: Group and index.
57.07
REF 2 SRC
(see above)
On the master drive, selects the source of D2D reference 2 broadcast to all followers.
The default value is P.03.13, ie,
.
Value pointer: Group and index.
57.08
FOLLOWER CW SRC
(see above)
Selects the source of the D2D control word sent to the followers. The parameter is effective on the
master drive, as well as submasters in a multicast message chain (see parameter
).
The default value is P.02.18, ie,
Value pointer: Group and index.
Содержание ACSM1 Series
Страница 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Страница 4: ......
Страница 34: ...Drive programming using PC tools 34 ...
Страница 86: ...Drive control and features 86 ...
Страница 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Страница 302: ...Parameter data 302 ...
Страница 422: ...Application program template 422 ...
Страница 430: ...Appendix A Fieldbus control 430 ...
Страница 500: ...Appendix D Application examples 500 ...
Страница 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Страница 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...