Group
12 DIGITAL IO
Settings for the digital inputs and outputs, and the relay output.
12
Firmware block:
DIO1
(6)
Selects whether DIO1 is used as a
digital input or as a digital output and
connects an actual signal to the
digital output. The block also shows
the DIO status.
Block outputs located in other
parameter groups
)
Firmware block:
DIO2
(7)
Selects whether DIO2 is used as a
digital or frequency input or as a
digital output and connects an actual
signal to the digital output. The block
also shows the DIO status.
Frequency input can be scaled with
standard function blocks. See chapter
Block outputs located in other
parameter groups
)
(page
Firmware block:
DIO3
(8)
Selects whether DIO3 is used as a
digital input or as a digital/frequency
output, connects an actual signal to
the digital/frequency output and
scales the frequency output. The
block also shows the DIO status.
Block outputs located in other
parameter groups
)
(page
)
12.01
DIO1 CONF
(see above)
Selects whether DIO1 is used as a digital input or as a digital output.
(0)
Output
DIO1 is used as a digital output.
(1)
Input
DIO1 is used as a digital input.
DIO1
18
TLF7 2 msec
(3)
12.01 DIO1 CONF
[ Output ]
< 12.04 DIO1 OUT PTR
[ STATUS WORD 2.2 ]
(4 / 6.02.READ Y RELAY)
2.03 DIO STATUS
2.03
Bit 0
DIO2
19
TLF7 2 msec
(4)
12.02 DIO2 CONF
[ Output ]
< 12.05 DIO2 OUT PTR
[ STATUS WORD 2.3 ]
(4 / 6.02.MODULATING)
12.14 DIO2 F MAX
[ 1000 Hz ]
12.15 DIO2 F MIN
[ 3 Hz ]
12.16 DIO2 F MAX SCALE
[ 1500 ]
12.17 DIO2 F MIN SCALE
[ 0 ]
2.03 DIO STATUS
2.03
Bit 1
2.10 DIO2 FREQ IN
DIO3
20
TLF7 2 msec
(5)
12.03 DIO3 CONF
[ Output ]
< 12.06 DIO3 OUT PTR
[ STATUS WORD 1.10 ]
(4 / 6.01.FAULT)
< 12.07 DIO3 F OUT PTR
[ SPEED ACT ]
(7 / 1.01)
12.08 DIO3 F MAX
[ 1000 Hz ]
12.09 DIO3 F MIN
[ 3 Hz ]
12.10 DIO3 F MAX SCALE
[ 1500 ]
12.11 DIO3 F MIN SCALE
[ 0 ]
2.03 DIO STATUS
2.03
Bit 2
2.11 DIO3 FREQ OUT
Содержание ACSM1 Series
Страница 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Страница 4: ......
Страница 34: ...Drive programming using PC tools 34 ...
Страница 86: ...Drive control and features 86 ...
Страница 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Страница 302: ...Parameter data 302 ...
Страница 422: ...Application program template 422 ...
Страница 430: ...Appendix A Fieldbus control 430 ...
Страница 500: ...Appendix D Application examples 500 ...
Страница 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Страница 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...