Fieldbus control through the embedded fieldbus interface (EFB) 361
Modbus holding register addresses
Modbus holding register addresses for the ABB Drives profile and
DCU Profile
The table below shows the default Modbus holding register addresses for the
drive data with the ABB Drives profile. This profile provides a converted 16-bit
access to the drive data.
Note:
Only the 16 least significant bits of the drive’s 32-bit Control and Status
Words can be accessed.
Note:
Bits 16 through 32 of the DCU Control/Status word are not in use if 16-bit
control/status word is used with the DCU Profile.
Register address
Register data (16-bit words)
400001
Default: Control word (
). See sections
(page
Control Word for the DCU Profile
(page
The selection can be changed using parameter
.
400002
Default: Reference 1 (
).
The selection can be changed using parameter
.
400003
Default: Reference 2 (
).
The selection can be changed using parameter
.
400004
Default: Status Word (
(page
Status Word for the DCU Profile
(page
The selection can be changed using parameter
.
400005
Default: Actual value 1 (
The selection can be changed using parameter
.
400006
Actual value 2 (
).
The selection can be changed using parameter
.
400007…400014
Data in/out 7…14.
Selected by parameters
400015
…
400089
Unused
400090
…
400100
Error code access. See section
Error code registers (holding registers
(page
).
400101
…
465536
Parameter read/write.
Parameters are mapped to register addresses according to
parameter
Содержание ACQ80
Страница 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Страница 2: ... Related documents are listed on page 13 ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Startup control with I O and ID run ...
Страница 34: ...34 Using the control panel ...
Страница 74: ...74 Program features ...
Страница 78: ...78 Control macros ...
Страница 380: ...380 Fieldbus control through a fieldbus adapter ...
Страница 384: ...384 Parameterization with Drive Composer ...
Страница 388: ...388 Parameterization with Automation builder drive manager ...