22 Startup, control with I/O and ID run
Direction test is optional, and requires
rotating the motor. Do not do this if it could
cause any risk, or if the mechanical set-up
does not allow it.
To do the direction test, select
Spin the
motor
and press
(
Next
).
Note
: During testing, make sure that the
pump motor is outside the well or tank and
pump is decoupled from the motor.
Press the Start key
on the control panel
to start the drive.
Check the direction of the motor.
If it is forward, select
Yes, motor is spinning
forward
and press
(
Next
) to continue.
If the direction is not forward, select
No, fix
direction
and press
(
Next
) to continue.
If you want to make a backup of the settings
made so far, select
Backup
and press
(
Next
).
If you do not want to make a backup, select
Not now
and press
(
Next
).
Forward direction
Reverse direction