Parameters 215
Shows application program revision of the
adapter module in format axyz, where a = major
revision number, xy = minor revision number, z =
correction number or letter.
Example: 190A = revision 1.90A.
0x0000
0x0000...0xffff
Application program version of adapter module.
-
52
Selection of data to be transferred from drive to
fieldbus controller through fieldbus adapter A.
Note:
32-bit values require two consecutive
parameters. Whenever a 32-bit value is selected
in a data parameter, the next parameter is
automatically reserved.
Parameters
select data to be
transferred from the drive to the fieldbus
controller through fieldbus adapter A.
None
None.
0
CW 16bit
Control Word (16 bits)
1
Ref1 16bit
Reference REF1 (16 bits)
2
Ref2 16bit
Reference REF2 (16 bits)
3
SW 16bit
Status Word (16 bits)
4
Act1 16bit
Actual value ACT1 (16 bits)
5
Act2 16bit
Actual value ACT2 (16 bits)
6
CW 32bit
Control Word (32 bits)
11
Ref1 32bit
Reference REF1 (32 bits)
12
Ref2 32bit
Reference REF2 (32 bits)
13
SW 32bit
Status Word (32 bits)
14
Act1 32bit
Actual value ACT1 (32 bits)
15
Act2 32bit
Actual value ACT2 (32 bits)
16
SW2 16bit
Status Word 2 (16 bits)
24
No.
Name/Value
Description
Def/
FbEq16
Содержание ACQ80
Страница 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Страница 2: ... Related documents are listed on page 13 ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Startup control with I O and ID run ...
Страница 34: ...34 Using the control panel ...
Страница 74: ...74 Program features ...
Страница 78: ...78 Control macros ...
Страница 380: ...380 Fieldbus control through a fieldbus adapter ...
Страница 384: ...384 Parameterization with Drive Composer ...
Страница 388: ...388 Parameterization with Automation builder drive manager ...