216 Parameters
Source selection (see
on
page
-
…
…
…
…
See parameter
53
Selection of data to be transferred from fieldbus
controller to drive through fieldbus adapter A.
Note:
32-bit values require two consecutive
parameters. Whenever a 32-bit value is selected
in a data parameter, the next parameter is
automatically reserved.
Parameters
select data to be
transferred from the fieldbus controller to the
drive through fieldbus adapter A.
None
None.
0
CW 16bit
Control Word (16 bits)
1
Ref1 16bit
Reference REF1 (16 bits)
2
Ref2 16bit
Reference REF2 (16 bits)
3
CW 32bit
Control Word (32 bits)
11
Ref1 32bit
Reference REF1 (32 bits)
12
Ref2 32bit
Reference REF2 (32 bits)
13
CW2 16bit
Control Word 2 (16 bits)
21
Source selection (see
on
page
-
…
…
…
…
See parameter
.
58
Configuration of the embedded fieldbus (EFB)
embedded fieldbus interface (EFB)
(page
).
Enables/disables the embedded fieldbus
interface and selects the protocol to use.
If you enable EFB with this parameter, panel port
can also be used as EFB port. For more
information, see section
on page
None
None (communication disabled).
0
Modbus RTU
Embedded fieldbus interface is enabled and uses
the Modbus RTU protocol.
1
No.
Name/Value
Description
Def/
FbEq16
Содержание ACQ80
Страница 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Страница 2: ... Related documents are listed on page 13 ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Startup control with I O and ID run ...
Страница 34: ...34 Using the control panel ...
Страница 74: ...74 Program features ...
Страница 78: ...78 Control macros ...
Страница 380: ...380 Fieldbus control through a fieldbus adapter ...
Страница 384: ...384 Parameterization with Drive Composer ...
Страница 388: ...388 Parameterization with Automation builder drive manager ...