110 Parameters
Shows value of analog input AI1 after scaling. See
parameters
and
.
This parameter is read-only.
50.000
-32768.000…
32767.000
Scaled value of analog input AI1.
1 = 1
Forced value that can be used instead of the true
reading of the input. See parameter
0
0.000…11.000 V Forced value of analog input AI1.
1000 = 1
unit
Selects the unit for readings and settings related
to analog input AI1.
Note: In firmware ASCL2 and ASCL4), this setting
must match the corresponding hardware setting
on the drive control unit. See chapter
Electrical
installation
, section
Switches
in the
Hardware
manual
of the drive and the default control
connections for the macro in use in chapter
(page
). Control board reboot
(either by cycling the power or through
parameter
) is required to
validate any changes in the hardware settings.
V
Volts.
2
mA
Milliamperes.
10
No.
Name/Value
Description
Def/
FbEq16