104 Parameters
Reserved
30...32
Supervision 1
(see page
).
33
Supervision 2
Bit 1 of
).
34
Supervision 3
).
35
Start delay
(see page
39
RO/DIO control
word bit0
(see page
). 40
RO/DIO control
word bit1
Bit 1 of
(see page
). 41
RO/DIO control
word bit2
(see page
). 42
PFC1
Not applicable.
PFC2
Not applicable.
PFC3
Not applicable.
PFC4
Not applicable.
Event word 1
Not applicable.
User load curve Not applicable.
RO/DIO control
word
Maps to corresponding bit in parameter
. For example, Bit 0 of
controls RO1, Bit 1 of
controls RO2, and so on.
Source selection (see
on
page
-
Defines the activation delay for relay output RO1. 0.0 s
t
On
t
Off
0.0 … 3000.0 s
Activation delay for RO1.
10 = 1 s
Defines the deactivation delay for relay output
RO1. See parameter
.
0.0 s
0.0 … 3000.0 s
Deactivation delay for RO1.
10 = 1 s
No.
Name/Value
Description
Def/
FbEq16
1
0
1
0
t
On
t
Off
t
On
t
Off
Status of
selected
source
RO status
Time
Содержание ACQ80
Страница 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Страница 2: ... Related documents are listed on page 13 ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Startup control with I O and ID run ...
Страница 34: ...34 Using the control panel ...
Страница 74: ...74 Program features ...
Страница 78: ...78 Control macros ...
Страница 380: ...380 Fieldbus control through a fieldbus adapter ...
Страница 384: ...384 Parameterization with Drive Composer ...
Страница 388: ...388 Parameterization with Automation builder drive manager ...