208 Parameters
Defines the trigger level for “above limit”
indication in frequency control. When actual
frequency exceeds the limit, bit 10 of
is set.
50.00 Hz
0.00…
1000.00 Hz
“Above limit” indication trigger level for
frequency control.
10 = 1
Defines the trigger level for the “kWh pulse” on
for 50 ms. The output of the pulse is bit 9 of
.
1.000 kWh
0.001…
1000.000 kWh
“kWh pulse” on trigger level.
1 = 1 kWh
Defines the number of decimal places of power-
related
parameters.
2
0...3
Number of decimal places of power parameters.
1 = 1
Defines the number of decimal places of current-
related
parameters.
1
0...3
Number of decimal places of current parameters. 1 = 1
49
Communication settings for the control panel
port on the drive.
Defines the node ID of the drive. All devices
connected to the network must have a unique
node ID.
Note: For networked drives, it is advisable to
reserve ID 1 for spare/replacement drives.
1
1…32
Node ID.
1 = 1
Defines the transfer rate of the link.
38.4 kbps
38.4 kbit/s.
1
57.6 kbps
57.6 kbit/s.
2
86.4 kbps
86.4 kbit/s.
3
115.2 kbps
115.2 kbit/s.
4
230.4 kbps
230.4 kbit/s.
5
Sets a timeout for control panel (or PC tool)
communication. If a communication break lasts
longer than the timeout, the action specified by
parameter
taken.
10.0 s
0.3…3000.0 s
Panel/PC tool communication timeout.
10 = 1 s
No.
Name/Value
Description
Def/
FbEq16
Содержание ACQ80
Страница 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Страница 2: ... Related documents are listed on page 13 ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Startup control with I O and ID run ...
Страница 34: ...34 Using the control panel ...
Страница 74: ...74 Program features ...
Страница 78: ...78 Control macros ...
Страница 380: ...380 Fieldbus control through a fieldbus adapter ...
Страница 384: ...384 Parameterization with Drive Composer ...
Страница 388: ...388 Parameterization with Automation builder drive manager ...