196 Parameters
Defines the time constant of the 1-pole filter
used to smooth the derivative component of the
process PID controller.
0.0 s
0.0…10.0 s
Filter time constant.
10 = 1 s
Defines the minimum limit for the process PID
controller output. Using the minimum and
maximum limits, it is possible to restrict the
operation range.
0.00
-100.00...100.00 Minimum limit for process PID controller output. 1 = 1
Defines the maximum limit for the process PID
controller output. See parameter
.
100.00
-100.00...100.00 Maximum limit for process PID controller output. 1 = 1
Freezes (or defines a source that can be used to
freeze) the output of the process PID controller,
keeping the output at the value it was before
freeze was enabled. This feature can be used
when, for example, a sensor providing process
feedback must to be serviced without stopping
the process.
1 = Process PID controller output frozen
See also parameter
.
Not selected
Process PID controller output not frozen.
0
Selected
Process PID controller output frozen.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
No.
Name/Value
Description
Def/
FbEq16
63
%
100
T
t
O = I × (1 - e
-t/T
)
I = filter input (step)
O = filter output
t
= time
T = filter time constant
Unfiltered signal
Filtered signal
Содержание ACQ80
Страница 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Страница 2: ... Related documents are listed on page 13 ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Startup control with I O and ID run ...
Страница 34: ...34 Using the control panel ...
Страница 74: ...74 Program features ...
Страница 78: ...78 Control macros ...
Страница 380: ...380 Fieldbus control through a fieldbus adapter ...
Страница 384: ...384 Parameterization with Drive Composer ...
Страница 388: ...388 Parameterization with Automation builder drive manager ...