Fault tracing 339
0002
Maximum speed limit or
calculated field
weakening point too low.
Check settings of parameters
•
•
•
•
•
.
Make sure that
•
> (0.55 ×
) >
(0.50 × synchronous speed)
•
< 0, and
• supply voltage > (0.66 ×
0003
Maximum torque limit
too low.
Check settings of parameter
, and
the torque limits in group
Make sure that the maximum
torque limit in force is greater
than 100%.
0004
Current measurement
calibration did not finish
within reasonable time
Contact your local ABB
representative.
0005…0008
Internal error.
Contact your local ABB
representative.
0009
(Asynchronous motors
only)
Acceleration did not
finish within reasonable
time.
Contact your local ABB
representative.
000A
(Asynchronous motors
only)
Deceleration did not
finish within reasonable
time.
Contact your local ABB
representative.
000B
(Asynchronous motors
only)
Speed dropped to zero
during ID run.
Contact your local ABB
representative.
000C
(Permanent magnet
motors only)
First acceleration did not
finish within reasonable
time.
Contact your local ABB
representative.
Code
(hex)
Fault / Aux. code
(
aux code visible only on
assistant control panel
and drive composer)
Cause
What to do
Содержание ACQ80
Страница 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Страница 2: ... Related documents are listed on page 13 ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Startup control with I O and ID run ...
Страница 34: ...34 Using the control panel ...
Страница 74: ...74 Program features ...
Страница 78: ...78 Control macros ...
Страница 380: ...380 Fieldbus control through a fieldbus adapter ...
Страница 384: ...384 Parameterization with Drive Composer ...
Страница 388: ...388 Parameterization with Automation builder drive manager ...