Parameters 267
Defines the cosphi of the motor for a more
accurate motor model. The value is not
obligatory, but is useful with an asynchronous
motor, especially when performing a standstill
identification run. With a permanent magnet or
synchronous reluctance motor, this value is not
needed.
Notes:
• Do not enter an estimated value. If you do not
know the exact value, leave the parameter at
zero.
• This parameter cannot be changed while the
drive is running.
0.00
0.00…1.00
Cosphi of the motor.
100 = 1
Defines the nominal motor shaft torque for a
more accurate motor model. Not obligatory. The
unit is selected by parameter
.
Note:
This parameter cannot be changed while
the drive is running.
0.000
N·m or
lb·ft
0.000…
4000000.000
N·m or 0.000…
2950248.597
lb·ft
Nominal motor torque.
1 = 100