232 Parameters
Shows cumulative calculated flow.
0.00
0.00...
21474836.00 m
3
Total flow.
1 = 1
Shows the ratio of pump flow rate and power
input.
0.00
0.00...32767.95
m
3
/kWh
Specific energy of the pump.
1 = 1
m
3
/kWh
Shows the estimated head produced by the
pump.
-
0.00...
32767.00 m
Estimated pump head.
1 = 1 m
Shows the measured flow of current day in cubic
meter.
Note:
You can reset this value using the
parameter
0.00
0.00...
21474836.00 m
3
Measured flow of the current day.
10 = 1
Shows the flow rate based on the counts
received from the sensors. This value is displayed
when the parameter
is
selected as
0
0...2147483648
Measured flow rate.
1 = 1
Selects the source for the flow feedback 1.
Not selected
Feedback not used.
0
AI1 scaled
(see page
).
1
AI2 scaled
(see page
).
2
Freq in scaled
(see page
3
AI1 percent
).
8
AI2 percent
).
9
Feedback data
storage
(see page
10
Source selection (see
on
page
-
Selects the source for the flow feedback 2.
Not selected
Feedback not used.
0
AI1 scaled
(see page
).
1
AI2 scaled
(see page
).
2
Freq in scaled
(see page
3
No.
Name/Value
Description
Def/
FbEq16
Содержание ACQ80
Страница 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Страница 2: ... Related documents are listed on page 13 ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Startup control with I O and ID run ...
Страница 34: ...34 Using the control panel ...
Страница 74: ...74 Program features ...
Страница 78: ...78 Control macros ...
Страница 380: ...380 Fieldbus control through a fieldbus adapter ...
Страница 384: ...384 Parameterization with Drive Composer ...
Страница 388: ...388 Parameterization with Automation builder drive manager ...