Parameters 141
Enables/disables temperature-based output
current limitation.
The limitation should only be disabled if required
by the application.
Disable
Thermal current limitation disabled.
0
Enable
Thermal current limitation enabled.
1
Selects a source that switches between two
different predefined adjustable speed limit sets.
0 = minimum speed limit defined by
and
maximum
speed limit defined by
are active
1 = minimum speed limit selected by
and
maximum speed limit defined by
are active.
The user can define two sets of speed limits, and
switch between the sets using a binary source
such as a digital
input.
The user can define two sets of speed limits, and
switch between the sets using a binary source
such as a digital input.
The first set of limits is defined by parameters
and
The second set has selector parameters for both
the minimum (
) and maximum (
) limits
that allows the use of a selectable analog source
(such as an analog input).
No.
Name/Value
Description
Def/
FbEq16
User-defined
minimum
speed limit
0
AI1
AI2
0
1
0
1
User-defined
maximum
speed limit
0
AI1
AI2
Содержание ACQ80
Страница 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Страница 2: ... Related documents are listed on page 13 ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Startup control with I O and ID run ...
Страница 34: ...34 Using the control panel ...
Страница 74: ...74 Program features ...
Страница 78: ...78 Control macros ...
Страница 380: ...380 Fieldbus control through a fieldbus adapter ...
Страница 384: ...384 Parameterization with Drive Composer ...
Страница 388: ...388 Parameterization with Automation builder drive manager ...