Parameters 265
Scalar
Scalar control. Suitable for most applications, if
top performance is not required.
Motor identification run is not required.
Note:
Scalar control must be used in the
following situations:
• with multimotor systems 1) if the load is not
equally shared between the motors, 2) if the
motors are of different sizes, or 3) if the
motors are going to be changed after the
motor identification (ID run)
• if the nominal current of the motor is less than
1/6 of the nominal output current of the drive
• if the drive is used with no motor connected
(for example, for test purposes).
Note
: Correct motor operation requires that the
magnetizing current of the motor does not
exceed 90% of the nominal current of the
inverter.
See section
(page
).
1
Defines the nominal motor current.
This value must be equal to the value on the
motor rating plate. If multiple motors are
connected to the drive, enter the total current of
the motors.
Notes
:
• Correct motor operation requires that the
magnetizing current of the motor does not
exceed 90% of the nominal current of the
drive.
• This parameter cannot be changed while the
drive is running.
1.8 A
0.0 …5.2 A
Nominal current of the motor. The allowable
range is 1/6…2 ×
I
N
of the drive (0…2 ×
I
N
with
scalar control mode).
1 = 1 A
No.
Name/Value
Description
Def/
FbEq16
Содержание ACQ80
Страница 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Страница 2: ... Related documents are listed on page 13 ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Startup control with I O and ID run ...
Страница 34: ...34 Using the control panel ...
Страница 74: ...74 Program features ...
Страница 78: ...78 Control macros ...
Страница 380: ...380 Fieldbus control through a fieldbus adapter ...
Страница 384: ...384 Parameterization with Drive Composer ...
Страница 388: ...388 Parameterization with Automation builder drive manager ...