76 Control macros
Default control connections for the ABB standard macro
Terminal size: 0.14…1.5 mm
2
Tightening torque: 0.5 N·m (0.4 lbf·ft)
1)
Ground the outer shield of the cable 360 degrees under the grounding clamp on the grounding shelf
for the control cables.
2)
Connected with jumpers at the factory.
3)
Use shielded twisted-pair cables for digital signals.
Max.
500 ohm
1…10 kohm
X1
Reference voltage and analog inputs and outputs
I/O available
in base unit
1
SCR
Signal cable shield (screen)
2
AI1
Not configured
3
AGND
Analog input circuit common
4
+10V
Reference voltage 10 V DC
5
AI2
Not configured
6
AGND
Analog input circuit common
7
AO1
Output frequency: 0...20 mA
8
AO2
Motor current
9
AGND
Analog output circuit common
X2 and X3 Aux. voltage output and programmable DIs
10
+24V
Aux. voltage 24 V DC, max. 250 mA
x
11
DGND
Aux. voltage output common for DIs
x
12
DCOM
Digital input common for all
x
13
DI1
Not configured
x
14
DI2
Not configured
x
15
DI3
Not configured
16
DI4
Not configured
17
DI5
Not configured
18
DI6
Not configured
X6, X7, X8 Relay output
19
RO1C
Ready run
250 V AC / 30 V DC
2 A
x
20
RO1A
x
21
RO1B
x
22
RO2C
Running
250 V AC / 30 V DC
2 A
23
RO2A
24
RO2B
25
RO3C
Fault (-1)
250 V AC / 30 V DC
2 A
26
RO3B
27
RO3A
X5
EIA-485 Modbus RTU
29
B+
Embedded Modbus RTU (EIA-485). See
embedded fieldbus interface (EFB)
.
30
A-
31
DGND
S100
TERM
Serial data link termination switch
Safe torque off
34
SGND
Safe torque off. Factory connection. Both
circuits must be closed for the drive to start.
See chapter Delete safe torque in drive
hardware manual.
x
35
OUT
x
36
IN1
x
37
IN2
x
3)
2)
1)
See the notes on
the next page.
2)
Содержание ACQ80
Страница 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Страница 2: ... Related documents are listed on page 13 ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Startup control with I O and ID run ...
Страница 34: ...34 Using the control panel ...
Страница 74: ...74 Program features ...
Страница 78: ...78 Control macros ...
Страница 380: ...380 Fieldbus control through a fieldbus adapter ...
Страница 384: ...384 Parameterization with Drive Composer ...
Страница 388: ...388 Parameterization with Automation builder drive manager ...