Parameters 173
Defines the start date of season 1 in format
dd.mm, where dd is the number of the day and
mm is the number of the month.
The season changes at midnight. One season can
be active at a time. Timers are started on
exception days even if they are not inside the
active season.
The season start dates (1…4) must be given in
increasing order to use all seasons. The default
value is interpreted that the season is not
configured. If the season start dates are not in
increasing order and the value is something else
than the default value, a season configuration
warning is given.
01.01.
01.01…31.12
Season start date.
-
Defines the start date of season 2.
See
.
01.01.
Defines the start date of season 3.
See
.
01.01.
Defines the start date of season 4.
See
.
01.01.
Defines how many of the exceptions are active by
specifying the last active one. All preceding
exceptions are active.
Exceptions 1…3 are periods (duration can be
defined) and exceptions 4…16 are days (duration
is always 24 hours).
Example:
If the value is 4, exceptions 1…4 are
active, and exceptions 5…16 are not active.
3
0…16
Number of active exception periods or days.
1 = 1
No.
Name/Value
Description
Def/
FbEq16
Содержание ACQ80
Страница 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Страница 2: ... Related documents are listed on page 13 ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Startup control with I O and ID run ...
Страница 34: ...34 Using the control panel ...
Страница 74: ...74 Program features ...
Страница 78: ...78 Control macros ...
Страница 380: ...380 Fieldbus control through a fieldbus adapter ...
Страница 384: ...384 Parameterization with Drive Composer ...
Страница 388: ...388 Parameterization with Automation builder drive manager ...