Parameters 157
Fault if running
If running, the drive trips on fault
3
Selects the signal to be monitored by signal
supervision function 2.
For the available selections, see parameter
.
Defines a filter time constant for the signal
monitored by signal supervision 2.
0.000 s
0.000 …
30.000 s
Signal filter time.
1000 = 1 s
Defines the lower limit for signal supervision 2.
0.00
-21474836.00…
21474836.00
Low limit.
-
Defines the upper limit for signal supervision 2.
0.00
-21474836.00…
21474836.00
Upper limit.
-
Defines the hysteresis for the signal monitored
by signal supervision 2.
0.00
0.00…
100000.00
Hysteresis.
-
Selects the mode of signal supervision
function 3.
Determines how the monitored signal (see
parameter
) is compared to its lower and
upper limits (
and
respectively). The
action to be taken when the condition is fulfilled
is selected by
Disabled
Signal supervision 3 not in use.
0
Low
Action is taken whenever signal is below
Supervision low limit - (0.5 * hysteresis). Action is
deactivated whenever signal is above
Supervision low limit + (0.5 * hysteresis).
1
High
Action is taken whenever signal is above
Supervision high limit + (0.5 * hysteresis). Action
is deactivated whenever signal is below
Supervision high limit - (0.5 * hysteresis).
2
Abs low
Action is taken whenever absolute value of signal
is below absolute value of Supervision low limit -
(0.5 * hysteresis). Action is deactivated whenever
absolute value of signal is above absolute value
of Supervision low limit + (0.5 * hysteresis).
3
No.
Name/Value
Description
Def/
FbEq16
Содержание ACQ80
Страница 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Страница 2: ... Related documents are listed on page 13 ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Startup control with I O and ID run ...
Страница 34: ...34 Using the control panel ...
Страница 74: ...74 Program features ...
Страница 78: ...78 Control macros ...
Страница 380: ...380 Fieldbus control through a fieldbus adapter ...
Страница 384: ...384 Parameterization with Drive Composer ...
Страница 388: ...388 Parameterization with Automation builder drive manager ...