340 Fault tracing
000D
(Permanent magnet
motors only)
Second acceleration did
not finish within
reasonable time.
Contact your local ABB
representative.
000E…0010
Internal error.
Contact your local ABB
representative.
0011
(Synchronous reluctance
motors only)
Pulse test error.
Contact your local ABB
representative.
0012
Motor too large for
advanced standstill ID
run.
Check that the motor and drive
sizes are compatible.
Contact your local ABB
representative.
0013
(Asynchronous motors
only)
Motor data error.
Check that the motor nominal
value settings in the drive are the
same as in the motor nameplate.
Contact your local ABB
representative.
FF63 STO diagnostics
failure.
SW internal malfunction. Reboot the control unit (using
or by cycling power.
FF81 FB A force trip
A fault trip command has
been received through
fieldbus adapter A.
Check the fault information
provided by the PLC.
FF8E EFB force trip
A fault trip command has
been received through
the embedded fieldbus
interface.
Check the fault information
provided by the PLC.
Code
(hex)
Fault / Aux. code
(
aux code visible only on
assistant control panel
and drive composer)
Cause
What to do
Содержание ACQ80
Страница 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Страница 2: ... Related documents are listed on page 13 ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Startup control with I O and ID run ...
Страница 34: ...34 Using the control panel ...
Страница 74: ...74 Program features ...
Страница 78: ...78 Control macros ...
Страница 380: ...380 Fieldbus control through a fieldbus adapter ...
Страница 384: ...384 Parameterization with Drive Composer ...
Страница 388: ...388 Parameterization with Automation builder drive manager ...