Fault tracing 327
4981 External
temperature 1
Measured temperature 1
has exceeded fault limit.
Check the value of parameter
Check the cooling of the motor
(or other equipment whose
temperature is being measured).
4982 External
temperature 2
Measured temperature 2
has exceeded fault limit.
Check the value of parameter
Check the cooling of the motor
(or other equipment whose
temperature is being measured).
4991 Safe motor
temperature
The CPTC-02 module
indicates
overtemperature:
• motor temperature is
too high, or
• the thermistor is in
shortcircuit.
Check the cooling of the motor.
Check the motor load and drive
ratings. Check the wiring of the
temperature sensor. Repair
wiring if faulty.
Measure the resistance of the
sensor. Replace the sensor if
faulty.
5080 Fan
Cooling fan is stuck or
disconnected.
Check fan operation and
connection. Replace fan if faulty.
5081 Auxiliary fan
broken
An auxiliary cooling fan is
stuck or disconnected.
1 – Auxiliary fan 1 broken
2 – Auxiliary fan 2 broken
Check auxiliary fan(s) and
connection(s). Replace fan if
faulty.
5089 SMT circuit
malfunction
Safe motor temperature
fault is generated and
STO
event/fault/warning is
not generated.
Check connection between the
relay output of the module and
the STO terminal.
0001
Auxiliary fan 1 broken.
0002
Auxiliary fan 2 broken.
5090 STO hardware
failure
STO hardware
diagnostics has detected
hardware failure.
Contact your local ABB
representative for hardware
replacement.
Code
(hex)
Fault / Aux. code
(
aux code visible only on
assistant control panel
and drive composer)
Cause
What to do
Содержание ACQ80
Страница 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Страница 2: ... Related documents are listed on page 13 ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Startup control with I O and ID run ...
Страница 34: ...34 Using the control panel ...
Страница 74: ...74 Program features ...
Страница 78: ...78 Control macros ...
Страница 380: ...380 Fieldbus control through a fieldbus adapter ...
Страница 384: ...384 Parameterization with Drive Composer ...
Страница 388: ...388 Parameterization with Automation builder drive manager ...