Startup, control with I/O and ID run 23
The first start is now complete and the drive
is ready for use.
Press
(
Done
) to enter the Home view.
The Home view monitoring the values of the
selected signals is shown on the control
panel.
2 – Parameters
For a basic startup, configure the below parameters:
=
/
for permanent
magnet motor
...
= As per motor name plate
Note:
For permanent magnet motors, enter motor back EMF value instead of
motor nominal voltage.
79.1 Solar status word1
79.11 Manual input source 1
79.41 Start DC voltage
79.42 PV cell min voltage/79.43 PV cell max voltage
79.51 Pump minimum speed
79.52 Pump maximum speed
= ABB recommends to keep this value higher than the value in
parameter
.
= As per PV array rating
= ABB recommends to keep this value 20% of motor
nominal rpm or more.
= Pump maximum speed in RPM