180 Parameters
Defines the warning limit for temperature
supervision function 1. When measured
temperature 1 exceeds the limit, warning
is generated.
The unit is selected by parameter
110 °C or
230 °F
-60…5000 °C or
-76…9032 °F
Warning limit for temperature monitoring
function 1.
1 = 1 unit
Specifies the analog input when the setting of
requires
measurement through an analog input.
Not selected
None.
0
AI1 actual value
Analog input AI1 on the control unit.
1
AI2 actual value Analog input AI2 on the control unit.
2
Source selection (see
on
page
-
Selects the source from which measured
temperature 2 is read.
Usually this source is from a sensor connected to
the motor controlled by the drive, but it could be
used to measure and monitor a temperature
from other parts of the process as long as a
suitable sensor is used as per the selection list.
Disabled
None. Temperature monitoring function 2 is
disabled.
0
Estimated
temperature
Estimated motor temperature (see parameter
).
The temperature is estimated from an internal
drive calculation. It is important to set up the
ambient temperature of the motor in
.
1
No.
Name/Value
Description
Def/
FbEq16
Содержание ACQ80
Страница 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Страница 2: ... Related documents are listed on page 13 ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Startup control with I O and ID run ...
Страница 34: ...34 Using the control panel ...
Страница 74: ...74 Program features ...
Страница 78: ...78 Control macros ...
Страница 380: ...380 Fieldbus control through a fieldbus adapter ...
Страница 384: ...384 Parameterization with Drive Composer ...
Страница 388: ...388 Parameterization with Automation builder drive manager ...