Parameters 109
Specifies the analog input limits to be
supervised. See parameter
.
0b0000
0b000...0b1111
Activation of analog input supervision.
1 = 1
Activates/deactivates analog input supervision
for each control location (see section
on page
When a control location does not utilize AI for
referencing, you can use this parameter to
deactivate the AI supervision (
). This hides
the warning or fault generated by AI supervision
function (
), for the selected control location.
For example, if
= Bit 0 or Bit 1 is 1
= Bit 0 is 0
then, AI1 supervision is masked in EXT1.
0b0000
0b000...0b1111
Activation/deactivation of analog input
supervision.
1 = 1
Shows value of analog input AI1 in mA or V
(depending on whether the input is set to current
or voltage by a hardware setting).
This parameter is read-only.
0.000
0.000…11.000 V
Value of analog input AI1.
1000 =
1 unit
No.
Name/Value
Description
Def/
FbEq16
Bit
Name
Description
0
AI1 < MIN
1 = Minimum limit supervision of AI1 active.
1
AI1 > MAX
1 = Maximum limit supervision of AI1 active.
2
AI2 < MIN
1 = Minimum limit supervision of AI2 active.
3
AI2 > MAX
1 = Maximum limit supervision of AI2 active.
4…15 Reserved
Bit
Name
Description
0
AI1 Ext1
1 = AI1 supervision is active when EXT1 is used.
1
AI1 Ext2
1 = AI1 supervision is active when EXT2 is used.
2
AI1 Local
1 = AI1 supervision is active when local control is used.
3
Reserved
4
AI2 Ext1
1 = AI2 supervision is active when EXT1 is used.
5
AI2 Ext2
1 = AI2 supervision is active when EXT2 is used.
6
AI2 Local
1 = AI2 supervision is active when local control is used.
7...15
Reserved
Содержание ACQ80
Страница 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Страница 2: ... Related documents are listed on page 13 ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Startup control with I O and ID run ...
Страница 34: ...34 Using the control panel ...
Страница 74: ...74 Program features ...
Страница 78: ...78 Control macros ...
Страница 380: ...380 Fieldbus control through a fieldbus adapter ...
Страница 384: ...384 Parameterization with Drive Composer ...
Страница 388: ...388 Parameterization with Automation builder drive manager ...