Program features 49
9. The drive waits until the parameter
is elapsed. A new
cleaning sequence starts or normal operation starts.
10. The pump starts following speed/frequency reference of the active control
location. During acceleration to speed/frequency, the drive follows pump
cleaning acceleration time
The operation of cleaning sequence is based on the selected triggering
conditions. See diagram on page
.
You can start the pump cleaning sequence as follows:
• On every start and stop.
• With DI4, DI5 or DI6.
• Based on the pump condition. For example, Supervision 1...3. See parameter
group
• Based on time interval defined by parameter
. For
example, at every 10 hours.
Note:
Pump cleaning is executed only once for every start after time is
elapsed.
• Based on real time clock (for example, at 01h:00min:00s) defined by
parameter
and based on timer configurations
• By selecting
in parameter
.
Notes:
• The start command is released automatically by firmware and is
independent of drive start command.
• Pump cleaning can be interrupted by removing the configured trigger.
• After pump cleaning cycles, normal pump operation is not automatically
resumed even when start command is active. You need to remove the
trigger manually and an acknowledgment of pump cleaning must be
given each time.
• If parameter
is set to
, then
after the pump cleaning cycle is completed, the drive resumes normal
operation.
• If pump cleaning is triggered using parameter
is activated at the same time,
then priority is given to parameter
.
• In local mode, no warnings are generated when trigger from parameter
is active. However, when the drive is switched to
external mode and the trigger is active, then the pump cleaning is
automatically started.
Содержание ACQ80
Страница 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Страница 2: ... Related documents are listed on page 13 ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Startup control with I O and ID run ...
Страница 34: ...34 Using the control panel ...
Страница 74: ...74 Program features ...
Страница 78: ...78 Control macros ...
Страница 380: ...380 Fieldbus control through a fieldbus adapter ...
Страница 384: ...384 Parameterization with Drive Composer ...
Страница 388: ...388 Parameterization with Automation builder drive manager ...