Program features 71
In addition, 10% of the dead-band value is added as dead-band hysteresis
positive and negative. This value is internally set in the firmware and cannot be
changed.
Notes:
AI dead-band (
) is applicable for both AI1 and AI2.
Example of using
dead-band in AI1 (voltage mode)
If,
= 50
= 0 - 10 V
then,
AI dead-band value = 10 * 50 * 0.01 = 5 V
AI Hysteresis value = 5 * 0.1 = 0.5 V
Hysteresis positive value = 5 + 0.5 = 5.5 V
Hysteresis negative value = 5 - 0.5 = 4.5 V
When AI1 input voltage increases, up to 5.5 V, the AI1 actual value (
)
displays zero. After AI1 input voltage reaches 5.5 V, the AI1 actual value displays
5.5 V and continues to display the detected value up to the maximum AI1
value10 V (
When AI1 input voltage decreases, the AI1 actual value displays the detected
value up to 4.5 V. From 4.5 V to zero, the AI1 actual value displays Zero till it
reaches 0V.
Example of using dead-band in AI1 (current mode)
If,
= mA
= 50
= 0 - 20 mA
then,
AI dead-band value = 20 * 50 * 0.01 = 10 mA
AI Hysteresis value = 10 * 0.1 = 1.0 mA
Hysteresis positive value = 10 + 1.0 = 11.0 mA
Hysteresis negative value = 10 - 1.0 = 9.0 mA
AI Hysteresis
AI dead-band value 10%
×
=
Содержание ACQ80
Страница 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Страница 2: ... Related documents are listed on page 13 ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Startup control with I O and ID run ...
Страница 34: ...34 Using the control panel ...
Страница 74: ...74 Program features ...
Страница 78: ...78 Control macros ...
Страница 380: ...380 Fieldbus control through a fieldbus adapter ...
Страница 384: ...384 Parameterization with Drive Composer ...
Страница 388: ...388 Parameterization with Automation builder drive manager ...