Fieldbus control through the embedded fieldbus interface (EFB) 353
2
REVERSE
1
Reverse direction of motor rotation. See in the
table below how this bit and sign of the reference
effect the direction of the motor direction.
0
(no op)
3
Reserved
4
RESET
0=>1
Fault reset if an active fault exists.
0
(no op)
5
EXT2
1
Select External control location EXT2. Effective if
the control location is parameterized to be
selected from the fieldbus.
0
Select External control location EXT1. Effective if
the control location is parameterized to be
selected from the fieldbus.
6
RUN_DISABLE
1
Run disable. If the drive is set to receive the run
enable signal from the fieldbus, this bit deactivates
the signal.
0
Run enable. If the drive is set to receive the run
enable signal from the fieldbus, this bit activates
the signal.
7
STOPMODE_RAMP
1
Normal ramp stop mode
0
(no op) Default to parameter stop mode if bits 7…9
are all 0.
8
STOPMODE_EMERG
ENCY_RAMP
1
Emergency ramp stop mode.
0
(no op) Default to parameter stop mode if bits 7…9
are all 0.
9
STOPMODE_COAST
1
Coast stop mode.
0
(no op) Default to parameter stop mode if bits 7…9
are all 0.
10
RAMP_PAIR _2
1
Not applicable.
0
Not applicable.
11
RAMP_OUT_ZERO
1
Force Ramp Function Generator output to zero.
Drive ramps to stop (current and DC voltage limits
in force).
0
Normal operation.
12
RAMP_HOLD
1
Halt ramping (Ramp Function Generator output
held).
0
Normal operation.
Bit
Name
Value State/Description
Sign of the reference
Positive (+)
Negative (-)
Bit REVERSE = 0
Forward
Reverse
Bit REVERSE = 1
Reverse
Forward
Содержание ACQ80
Страница 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Страница 2: ... Related documents are listed on page 13 ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Startup control with I O and ID run ...
Страница 34: ...34 Using the control panel ...
Страница 74: ...74 Program features ...
Страница 78: ...78 Control macros ...
Страница 380: ...380 Fieldbus control through a fieldbus adapter ...
Страница 384: ...384 Parameterization with Drive Composer ...
Страница 388: ...388 Parameterization with Automation builder drive manager ...