96 Parameters
Drive status word 1.
This parameter is read-only.
0b0000
0b0000...0b1111 Drive status word 1.
1 = 1
Drive status word 2.
This parameter is read-only.
0b0000
0b0000...0b1111 Drive status word 2.
1 = 1
No.
Name/Value
Description
Def/
FbEq16
Bit Name
Description
0
Enabled
Not applicable.
1
Inhibited
1 = Start inhibited. To start the drive, the inhibiting
signal (see par.
) must be removed and the start
signal cycled.
2
DC charged
1 = DC circuit has been charged
3
Ready to start
1 = Drive is ready to receive a start command
4
Following
reference
1 = Drive is ready to follow given reference
5
Started
1 = Drive has been started
6
Modulating
1 = Drive is modulating (output stage is being
controlled)
7
Limiting
1 = Any operating limit (speed, torque, etc.) is active
8
Local control
1 = Drive is in local control
9
Network control 1 = Drive is in
(see page
10 Ext1 active
1 = Control location EXT1 active
11
Ext2 active
1 = Control location EXT2 active
12 Reserved
13 Start request
1 = Start requested. 0 = When Enable to rotate signal is 0
(rotating of the motor is disabled).
14 Running
1 = Drive is controlling speed or frequency, in PID sleep
or pre-magnetization.
15 Reserved
Bit
Name
Description
0
Identification run
done
1 = Motor identification (ID) run has been performed
1
Magnetized
1 = The motor has been magnetized
2
Reserved
3
Speed control
1 = Speed control mode active
4...9
Reserved
10
Above limit
1 = Actual speed or frequency equals or exceeds
limit
(defined by parameters
). Valid in both
directions of
rotation.
11...12 Reserved
13
Start delay active
1 = Start delay (par.
) active.
14…15 Reserved
Содержание ACQ80
Страница 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Страница 2: ... Related documents are listed on page 13 ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Startup control with I O and ID run ...
Страница 34: ...34 Using the control panel ...
Страница 74: ...74 Program features ...
Страница 78: ...78 Control macros ...
Страница 380: ...380 Fieldbus control through a fieldbus adapter ...
Страница 384: ...384 Parameterization with Drive Composer ...
Страница 388: ...388 Parameterization with Automation builder drive manager ...