Parameters 177
35
Motor thermal protection settings such as
temperature measurement configuration, load
curve definition and motor fan control
configuration.
See also section
(page
).
Shows motor temperature as estimated by the
internal motor thermal protection model (see
parameters
). The unit is selected by
parameter
.
This parameter is read-only.
0
-60…1000 °C or
-76…1832 °F
Estimated motor temperature.
1 = 1°C
Shows temperature received through the source
defined by parameter
The unit is selected by parameter
Note:
With a PTC sensor, the value shown is not a
valid measurement. Either 0 ohm (normal
temperature) or the value of parameter
(excessive temperature)
is shown.
This parameter is read-only.
0
-60…5000 °C or
-76…9032 °F
Measured temperature 1.
1 = 1 unit
Shows temperature received through the source
defined by parameter
The unit is selected by parameter
Note:
With a PTC sensor, the value shown is not a
valid measurement. Either 0 ohm (normal
temperature) or the value of parameter
(excessive temperature)
is shown.
This parameter is read-only.
0
-60…5000 °C or
-76…9032 °F
Measured temperature 2.
1 = 1 unit
Motor overload level as a percentage of the fault
limit.
0.0
0.0...300.0 %
Motor overload level
1 = 1unit
No.
Name/Value
Description
Def/
FbEq16
Содержание ACQ80
Страница 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Страница 2: ... Related documents are listed on page 13 ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Startup control with I O and ID run ...
Страница 34: ...34 Using the control panel ...
Страница 74: ...74 Program features ...
Страница 78: ...78 Control macros ...
Страница 380: ...380 Fieldbus control through a fieldbus adapter ...
Страница 384: ...384 Parameterization with Drive Composer ...
Страница 388: ...388 Parameterization with Automation builder drive manager ...