264 Parameters
99
Motor configuration settings.
Selects the motor type.
Note:
This parameter cannot be changed while
the drive is running.
Asynchronous
motor
Standard squirrel cage AC induction motor
(asynchronous induction motor).
0
Permanent
magnet motor
Permanent magnet motor.
Three-phase AC synchronous motor with
permanent magnet rotor and sinusoidal
BackEMF voltage.
Note:
With permanent magnet motors special
attention must be paid on setting the motor
nominal values correctly in parameter group
. You must use vector control.
If the nominal BackEMF voltage of the motor is
not available, a full ID run should be performed
for improving performance.
1
PMaSynRM
Permanent magnet assisted Synchronous
Reluctance Motor.
2
Selects the motor control mode.
Vector
Vector control. Vector control has better
accuracy than scalar control but cannot be used
in all situations (see selection
below).
Requires motor identification run (ID run). See
parameter
Note:
In vector control the drive performs a
standstill ID run at the first start if ID run has not
been previously performed. A new start
command is required after standstill ID run.
Note:
To achieve a better motor control
performance, you can perform a normal ID run
without load.
See also section
(page
).
0
No.
Name/Value
Description
Def/
FbEq16
Содержание ACQ80
Страница 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Страница 2: ... Related documents are listed on page 13 ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Startup control with I O and ID run ...
Страница 34: ...34 Using the control panel ...
Страница 74: ...74 Program features ...
Страница 78: ...78 Control macros ...
Страница 380: ...380 Fieldbus control through a fieldbus adapter ...
Страница 384: ...384 Parameterization with Drive Composer ...
Страница 388: ...388 Parameterization with Automation builder drive manager ...