Parameters 223
Not applicable
Defines the mapping between parameters and
holding registers in the 400101…465535 Modbus
register range.
Changes to this parameter take effect after the
control unit is rebooted or the new settings
validated by parameter
).
Mode 0
16-bit values (groups 1…99, indexes 1…99):
Register address = 100 × parameter
group + parameter index.
32-bit values (groups 1…99, indexes 1…99):
Register address = 200 × parameter
group + 2 × parameter index.
0
Mode 1
16-bit values (groups 1…255, indexes 1…255):
Register address = 256 × parameter
group + parameter index.
1
Mode 2
32-bit values (groups 1…127, indexes 1…255):
Register address = 512 × parameter
group + 2 × parameter index.
2
Selects in which order 16-bit registers of 32-bit
parameters are transferred.
For each register, the first byte contains the high
order byte and the second byte contains the low
order byte.
Changes to this parameter take effect after the
control unit is rebooted or the new settings
validated by parameter
).
HI-LO
The first register contains the high order word,
the second contains the low order word.
0
LO-HI
The first register contains the low order word,
the second contains the high order word.
1
No.
Name/Value
Description
Def/
FbEq16
Содержание ACQ80
Страница 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Страница 2: ... Related documents are listed on page 13 ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Startup control with I O and ID run ...
Страница 34: ...34 Using the control panel ...
Страница 74: ...74 Program features ...
Страница 78: ...78 Control macros ...
Страница 380: ...380 Fieldbus control through a fieldbus adapter ...
Страница 384: ...384 Parameterization with Drive Composer ...
Страница 388: ...388 Parameterization with Automation builder drive manager ...