5.8 Peripheral Devices
5-91
5
(3) Dimensional Drawings
5.8.17 DeviceNet I/F Unit
(1) Model: JUSP-NS300
(2) Specifications
(24) (0.94)
CN6A
Units: mm (in) Approx. mass: 0.2 kg (0.44 lb)
NS100
S
W
1
20
(0.79)
128 (5.04)
142 (5.59)
(100)
(3.94)
(2) (0.08)
S
W
2
A
R
C
N
6
A
C
N
6
B
C
N
4
Nameplate
CN6B
CN4
FG terminal
Connector
to SERVOPACK
M4
Item
Details
Applicable SERVOPACK
All SGDH-
E models
Installation Method
Mounted on the SGDH SERVOPACK side: CN10.
Basic
Specifications
Power Supply Method
Supplied from the SERVOPACK control power supply.
Power Consumption
1.3 W
DeviceNet
Communications
Baud Rate Setting
Select from 125 kbps, 250 kbps, or 500 kbps using a rotary switch.
Node Address Setting
Select the address from 0 to 63 using the rotary switches.
Command Format
Operation Specifications
Positioning using DeviceNet communications.
Reference Input
DeviceNet communications
Commands: Motion commands (position, speed), and Parameter
read/write
Position Control
Functions
Acceleration/
Deceleration Method
Linear first/second-step, asymmetric, exponential, S-curve
Fully Closed Control
Possible
Input Signals
Fixed Allocation to SER-
VOPACK CN1 Connector
Forward/reverse run prohibited, Zero point signal, Emergency stop
signal
Internal Functions
Position Data Latch
Function
Position data latching is possible using phase C, zero point signals,
and external signals.
Protection
Parameters damage, Parameter setting errors, Communications error,
etc.
LED Indicators
MS: Module Status
NS: Network Status
Summary of Contents for SGDH