5 Specifications and Dimensional Drawings of Cables and Peripheral Devices
5.8.11 Magnetic Contactor
5-82
(3) Magnetic Contactor with Coil Drive Unit for Three-phase 400 V SERVOPACKs
The magnetic contactors for three-phase 400 V SERVOPACKs include coil drive unit.
The rated voltage of the operating coil in the coil drive unit is 24 VDC.
Maintain the power supply voltage within the specified range. The voltage below the allowable range causes
malfunction, resulting in the magnetic contacts seizing or the coil burning out.
If a voltage above 24 V is applied, the unit will be damaged. Confirm the voltage at the trial operation after
installation.
(a) Ratings and Specifications
(b) Circuit Connection Diagram
Model
TCU-500U
Input (operation)
Section
Rated Voltage
24 VDC
Allowable Voltage Fluc-
tuation
70 to 130% of the rated voltage
Current Range
7.3 to 9.3 mA
Operating Voltage
Maximum 70% of the rated voltage (at 23
°
C) (73.40
°
F)
Open Voltage
Minimum 10% of the raged voltage (at 23
°
C) (73.40
°
F)
Output Section
Output Method
High-sensitivity relay contacts
Max. Rated Voltage and
Current
220 VAC, 2 A
Rated Insulation Voltage
250 VAC
Operation Time
3 ms
Reset Time
1 ms
Operating Temperature
-20 to +55
°
C (
−
4 to 131 °F)
Surge Suppress-
ing Performance
Max. Rated Voltage
220 VAC
Rated Insulation Voltage
250 VAC
Surge Voltage Control
Method
CR method
Applicable Voltage
Range for Operation
Magnetic Coil
Any voltage between 100 VAC and 220 VAC
Examples:
• 100 V 50 Hz 100 to 110 V 60 Hz
• 200 V 50 Hz 200 to 220 V 60 Hz